| 3C | 
217 | 
Fan not working. | 
Check and, if necessary, replace the fan connector cable or the fan. | 
| 3L | 
214 | 
Fan is turned off during the safety period. | 
Check and, if necessary, replace the fan connector cable or the fan. | 
| 3P | 
216 | 
Fan is too slow. | 
Check and, if necessary, replace the fan connector cable or the fan. | 
| 3Y | 
215 | 
Fan is too fast. | 
Check and, if necessary, replace the fan connector cable or the fan. 
Check the flue gas system, clean or repair if necessary. | 
| 4C | 
224 | 
Temperature limiter of the heat exchanger or flue temperature has been triggered. | 
- Check for interruptions or short circuits and, if necessary, replace the heat exchanger temperature limiter and the connection cable.
 
- Check for interruptions or short circuits and, if necessary, replace the flue temperature limiter and the connection cable.
 
- Check the operating pressure in the heating system.
 
- Check and, if necessary, replace the temperature limiter.
 
- Check the pump start-up, and if necessary, replace it.
 
- Bleed the boiler.
 
- Check the heat exchanger on the water side, and if necessary, replace it.
 
- For boilers with reverse cylinders in the heat exchanger: check if they are installed properly.
 
 
 | 
| 4U | 
222 | 
Supply temperature sensor damaged (short circuit). | 
Check the temperature sensor and connection cable for interruptions or short circuits, replace if necessary. | 
| 4Y | 
223 | 
Supply temperature sensor damaged (interruption). | 
Check the temperature sensor and connection cable for interruptions or short circuits, replace if necessary. | 
| 6A | 
227 | 
Flame not confirmed. | 
- Check the effectiveness of the protective conductor connection.
 
- Check if the gas valve is open.
 
- Check the gas pressure at the connection (Æ page 48).
 
- Check the electrical connection.
 
- Check the electrodes and cables, and replace if necessary.
 
- Check the flue system, clean or repair if necessary.
 
- Check the gas-to-air ratio, adjust if necessary.
 
- If using natural gas, check and replace the external gas flow protection (pressure switch) if necessary.
 
- For operation dependent on room air, check the “room connection” or ventilation/air intake openings.
 
- Clean the condensate siphon outlet.
 
- Remove the membrane from the fan inlet nozzle and check for cracks or contamination.
 
- Clean the heat exchanger.
 
- Check and replace the gas fittings if necessary.
 
- Correctly insert the KIM, replace if necessary.
 
- For two-phase networks (IT): install a 2 W resistor on the network connection of the printed circuit board.
 
 
 | 
| 6C | 
228 | 
Flame detected despite the boiler being off. | 
- Check the electrodes, and replace if necessary.
 
- Check the flue system, clean or repair if necessary.
 
- Check if the printed circuit board is wet, dry if necessary.
 
 
 | 
| 6C | 
306 | 
Flame detected after the gas was turned off. | 
- Check and replace the gas fittings if necessary.
 
- Clean the condensate siphon.
 
- Check the electrodes and connection cables, and replace if necessary.
 
- Check the flue system, clean or repair if necessary.
 
 
 | 
| 7L | 
261 | 
Time error during the first safety time. | 
Replace the base controller BC25. | 
| 7L | 
280 | 
Time error during the restart attempt. | 
Replace the base controller BC25. | 
| 9L | 
234 | 
Gas valve coil or connection cable is damaged. | 
- Check the wiring, replace if necessary.
 
- Replace the gas valve.
 
 
 | 
| 9L | 
238 | 
Gas valve is damaged. | 
- Check the wiring, replace if necessary.
 
- Replace the gas valve.
 
 
 | 
| 9P | 
239 | 
KIM not recognized. | 
Correctly insert the KIM, replace if necessary. | 
| EL | 
259 | 
Damaged KIM or Logamatic BC25. | 
- Replace the KIM.
 
- Replace the base controller BC25.
 
 
 |