Buderus Logamax Plus GB172

Operating and Fault Indications Displayed on the Display

Fault Code Working Code Description
-A 208 The boiler is in the chimney sweep mode. After 15 minutes, the chimney sweep mode will be automatically deactivated.
-H 200 The boiler is in heating mode.
=H 201 The boiler is in DHW mode.
0A 202 Button lock active: the time interval for reactivating the burner has not yet been reached (Æ service function 2.3b).
0C 283 The burner start is in progress.
0E 265 The heat demand is lower than the boiler’s minimum heating power. The boiler operates in on/off mode.
0H 203 The boiler is in standby mode, with no heat demand.
0L 284 The gas valve is opening, the first safety time.
0U 270 The boiler is reaching high power.
0Y 204 The current supply temperature is higher than the set supply temperature. The boiler is turning off.
2E 357 The venting function is active.
2H 358 The protection against blocking the heating pump and the three-way valve is active.
2P 342 Speed growth limitation (gradient): too rapid temperature increase in DHW mode.
5H 268 The boiler is in a regulation system test.

Transient Faults

Fault Code Working Code Description Method of Removal
0Y 276 The temperature on the supply temperature sensor is > 95 °C. This fault message may appear without a fault if all radiator valves are suddenly closed.

  • Check the operating pressure in the heating system.
  • Fully open the service valves. Electrically connect the heating pump to the base controller BC25.
  • Start the heating pump or replace it.
  • Properly set the pump performance or characteristics and adjust to maximum power.
  • Check the supply temperature and connection cable for interruptions or short circuits, replace if necessary.
2P 341 Gradual limitation: too rapid temperature increase in heating mode.
  • Check the operating pressure in the heating system.
  • Fully open the service valves.
  • Electrically connect the heating pump to the base controller BC25.
  • Start the heating pump or replace it.
  • Set the pump’s performance or characteristics correctly and adjust to the maximum power.
3A 264 Fan failure during operation. Check and replace the fan connector cable or the fan if necessary.
3F 273 The burner and fan worked continuously for 24 hours and will be temporarily switched off for safety control.
4C 224 The exchanger temperature limiter or flue temperature limiter has been triggered. If the transient fault persists for a longer period, it will change into a permanent fault.
4U 350 Supply temperature sensor defective (short circuit). If the fault persists for a longer period, the fault code 4U and working code 222 will be shown.
4Y 351 Supply temperature sensor defective (interruption). If the fault persists for a longer period, the fault code 4Y and working code 223 will be shown.
6A 227 Flame not confirmed. After the 4th ignition attempt, the transient fault will become a permanent fault (non-transient).
6L 229 No ionization signal during burner operation. The burner will restart. If the ignition attempt fails, the transient fault 6A will be shown, and after the 4th ignition attempt, the transient fault will become a permanent fault.
8Y 232 Thermal protection AT90 has been triggered.
  • Check the settings of the thermal protection AT90 sensor.
  • Check the settings of the heating controller.
8Y 232 Thermal protection AT90 is defective.
  • Check the temperature sensor and connection cable for interruptions or short circuits, replace if necessary.
8Y 232 Missing bridge on the connection terminals for the external thermal protection AT90.
  • If the thermal protection is not connected, install the bridge.
8Y 232 Blocked thermal protection. Condensate pump failure.
  • Unblock the thermal protection.
  • Check the condensate drainage.
  • Replace the condensate pump.
EL 290 Damaged base controller BC25.
  • Replace the base controller BC25.

Non-Transient Faults

 

Fault Code Working Code Description How to Fix
3C 217 Fan not working. Check and, if necessary, replace the fan connector cable or the fan.
3L 214 Fan is turned off during the safety period. Check and, if necessary, replace the fan connector cable or the fan.
3P 216 Fan is too slow. Check and, if necessary, replace the fan connector cable or the fan.
3Y 215 Fan is too fast. Check and, if necessary, replace the fan connector cable or the fan.
Check the flue gas system, clean or repair if necessary.
4C 224 Temperature limiter of the heat exchanger or flue temperature has been triggered.
  • Check for interruptions or short circuits and, if necessary, replace the heat exchanger temperature limiter and the connection cable.
  • Check for interruptions or short circuits and, if necessary, replace the flue temperature limiter and the connection cable.
  • Check the operating pressure in the heating system.
  • Check and, if necessary, replace the temperature limiter.
  • Check the pump start-up, and if necessary, replace it.
  • Bleed the boiler.
  • Check the heat exchanger on the water side, and if necessary, replace it.
  • For boilers with reverse cylinders in the heat exchanger: check if they are installed properly.
4U 222 Supply temperature sensor damaged (short circuit). Check the temperature sensor and connection cable for interruptions or short circuits, replace if necessary.
4Y 223 Supply temperature sensor damaged (interruption). Check the temperature sensor and connection cable for interruptions or short circuits, replace if necessary.
6A 227 Flame not confirmed.
  • Check the effectiveness of the protective conductor connection.
  • Check if the gas valve is open.
  • Check the gas pressure at the connection (Æ page 48).
  • Check the electrical connection.
  • Check the electrodes and cables, and replace if necessary.
  • Check the flue system, clean or repair if necessary.
  • Check the gas-to-air ratio, adjust if necessary.
  • If using natural gas, check and replace the external gas flow protection (pressure switch) if necessary.
  • For operation dependent on room air, check the “room connection” or ventilation/air intake openings.
  • Clean the condensate siphon outlet.
  • Remove the membrane from the fan inlet nozzle and check for cracks or contamination.
  • Clean the heat exchanger.
  • Check and replace the gas fittings if necessary.
  • Correctly insert the KIM, replace if necessary.
  • For two-phase networks (IT): install a 2 W resistor on the network connection of the printed circuit board.
6C 228 Flame detected despite the boiler being off.
  • Check the electrodes, and replace if necessary.
  • Check the flue system, clean or repair if necessary.
  • Check if the printed circuit board is wet, dry if necessary.
6C 306 Flame detected after the gas was turned off.
  • Check and replace the gas fittings if necessary.
  • Clean the condensate siphon.
  • Check the electrodes and connection cables, and replace if necessary.
  • Check the flue system, clean or repair if necessary.
7L 261 Time error during the first safety time. Replace the base controller BC25.
7L 280 Time error during the restart attempt. Replace the base controller BC25.
9L 234 Gas valve coil or connection cable is damaged.
  • Check the wiring, replace if necessary.
  • Replace the gas valve.
9L 238 Gas valve is damaged.
  • Check the wiring, replace if necessary.
  • Replace the gas valve.
9P 239 KIM not recognized. Correctly insert the KIM, replace if necessary.
EL 259 Damaged KIM or Logamatic BC25.
  • Replace the KIM.
  • Replace the base controller BC25.

Faults not displayed on the screen

Boiler faults How to fix
Too loud combustion noise; growling
  • Correctly insert the KIM, replace if necessary.
  • Check the type of gas.
  • Check the gas pressure at the connection.
  • Check the flue system, clean or repair if necessary.
  • Check the gas-to-air ratio in the combustion air and flue gases, replace the gas valve if necessary.
Flow noises Set the correct performance or characteristic of the pump and adjust to maximum power.
Heating takes too long Set the correct performance or characteristic of the pump and adjust it to maximum power.
Flue gas values are incorrect; too high CO levels
  • Check the type of gas.
  • Check the gas pressure at the connection.
  • Check the flue system, clean or repair if necessary.
  • Check the gas-to-air ratio in the flue gases, replace the gas valve if necessary.
Poor, too hard ignition
  • Check the type of gas.
  • Check the gas pressure at the connection.
  • Check the electrical connection.
  • Check the electrodes with cables and replace if necessary.
  • Check the flue system, clean or repair if necessary.
  • Check the gas-to-air ratio, replace the gas valve if necessary.
  • For natural gas: check the external (additional) gas flow protection, replace if necessary.
  • Check the burner, replace if necessary.
Domestic hot water has a bad smell or dark color
  • Perform a thermal disinfection of the domestic hot water circuit.
  • Replace the protective anode.
Condensate in the air chamber Install or replace the membrane in the mixing unit according to the installation instructions.
Function unavailable (display remains dark)
  • Check the electrical connection.
  • Check the fuse, replace it if necessary.